01 / Establish a healthy circuit
109.09 mA. Real model includes 0.6 Ω supply/protection, 0.1 Ω switch and 0.02 Ω link; parallel coil and lamp also load the source.
Numeric response: 109.0909 mA; tolerance ±0.2 mA.
Electrical Fault-Finding Laboratory • 24 V DC • 8 November 2026
Five activities of approximately 15–25 minutes each. Learners should record evidence and explain parallel paths. Accept sensible rounding within the tolerances below. This guide is public teaching support, not secure assessment material.
109.09 mA. Real model includes 0.6 Ω supply/protection, 0.1 Ω switch and 0.02 Ω link; parallel coil and lamp also load the source.
Numeric response: 109.0909 mA; tolerance ±0.2 mA.
P = I²R = 0.10² × 120 = 1.20 W. A real current measurement includes the meter burden; the simulated shunt is 0.1 Ω.
Numeric response: 1.2000 W; tolerance ±0.02 W.
0 A in the open branch (except negligible voltmeter loading). Coil and indicator may remain energised. S-to-L resistance is not necessarily OL: the coil and R1+R2 provide a return path. With S1 open: 1200 + 220 = 1420 Ω.
Numeric response: 0.0000 A; tolerance ±0.0001 A.
2.571 V. The actual model is slightly lower due to supply and switch resistance. The faulty R1 section takes about 21.43 V in the ideal series calculation.
Numeric response: 2.5714 V; tolerance ±0.03 V.
20 mA, P = 0.48 W. Open coil: no coil current and no contact actuation. Bus short: finite pre-trip current set by source/wiring/short resistance; after Q1 opens, source branch current is zero. This is not a time-current fuse model.
Numeric response: 20.0000 mA; tolerance ±0.1 mA.
An ohmmeter applies a test signal; an energised source invalidates the measurement and may damage real equipment. Opening S1 alone leaves the protected bus live.
Parallel paths remain through the coil and the load branch. With S1 open, the open J1 has 1200 + 220 = 1420 Ω around the other path.
Measure voltage drop across each section under load. The added resistance takes a disproportionate share of supply voltage.
The low-resistance shunt creates a fault path. The model solves its finite current and latches the meter fuse and, where applicable, Q1 open.
An open relay coil cannot develop magnetic actuation even when voltage exists across its terminals. An open lamp can also be dark, so isolated resistance and contact/output measurements distinguish causes.
Reset is allowed only with supply isolated. The fault trips Q1 again on re-energisation; the cause must be removed.
No. It measures the equivalent network between probes, including parallel paths. Isolate one end in real practice where appropriate; this fixed trainer supports J1/S1 isolation only.
Examples: inductive transients, coil flyback, lamp temperature dependence, tolerances, arcing, thermal fuse behaviour and real time-current curves.
Supply enabled, S1/J1 closed, voltage probes PS/0. Values below include finite source and wiring resistance. Direct PS/0 voltmeter loading does not change the downstream circuit.
| Fault | Source A | P V | S V | X V | K V |
|---|---|---|---|---|---|
| healthy | 0.227667 | 23.863400 | 23.850572 | 13.008220 | 23.853461 |
| open | 0.119598 | 23.928241 | 23.926247 | 0.000000 | 23.918275 |
| high | 0.140881 | 23.915471 | 23.911344 | 2.561884 | 23.905511 |
| coil | 0.108735 | 23.934759 | 23.923885 | 13.048206 | 0.000000 |
| lamp | 0.128597 | 23.922842 | 23.909982 | 13.040623 | 23.922842 |
| welded | 0.227667 | 23.863400 | 23.850572 | 13.008220 | 23.853461 |
Bus short: Q1 opens, final downstream source current 0 A. PS remains at 24 V while enabled. To distinguish welded contact, open S1: the coil releases but the indicator remains supplied through the welded contact.
Correct socket and instrument mode; three or more useful readings; units and apparatus states; calculations; alternative faults considered; diagnosis linked to evidence; model limitations recognised. Independent mode requires a minimum evidence count, but an accepted diagnosis is not proof of diagnostic competence.
No verified qualification references are published. Use the mapping template to verify current official specifications before claiming coverage.